ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Rating - 2 Hr F Rating - 2 Hr
T Rating - 0 Hr FT Rating - 0 Hr
   FH Rating - 2 Hr
   FTH Rating - 0 Hr
    1. Wall Assembly — Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3 ) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.

      See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

    2. Cables — Aggregate cross-sectional area of cables in Smooth Sleeve to be min 8 percent to max 48 percent of the aggregate cross-sectional area of the Smooth Sleeve. Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types and sizes of cables may be used:
      A. Max 200 pair No. 24 AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) jacketing and insulation.
      B. Max 1/C, 750 kcmil power cable with copper conductors and cross-linked polyethylene (XLPE) jacketing.
      C. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation and jacket.
      D. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation and jacket.
      E. Max 7/C No. 2/0 AWG (or smaller) multiconductor power and control cables with XLPE or PVC insulation and XLPE or PVC jacket.
      F. Max RG59/U (or smaller) coaxial cable with fluorinated ethylene insulation and jacketing.
      G. Max 62.5/48 fiber optic cable with PVC insulation and jacketing.
      H. Max 4 pair No. 24 AWG (or smaller) copper conductor category 5 with Hylar insulation and jacket.
    3. Firestop System — The firestop system shall consist of the following:
      A. Firestop Device* — Smooth steel sleeve device incorporating flat washers secured by sliding compression couplers. Device shall be installed around cables in accordance with the accompanying installation instructions. Device provided in nom 1, 2 and 4 in. (25, 51 and 102 mm) sizes. Max diam of opening in wall for 1, 2 and 4 in. (25, 51 and 102 mm) size devices are 1-1/4, 2-7/16 and 4-1/2 in. (32, 62 and 114 mm) respectively.

      UNIQUE FIRE STOP PRODUCTS INC — Smooth Firestop


      B. Fill, Void or Cavity Material* - Putty — Min 1 in. (25 mm) thickness of fill material applied within the Smooth Sleeve, flush with both ends.

      RECTORSEALMetacaulk Fire Rated Putty


XHEZ.W-J-3109 W-J-3109 XHEZ 184960001 SYSTEM Active 20150902 20150902 184960001 613495002