ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Rating — 2 Hr F Rating — 2 Hr
T Rating — 1 Hr FT Rating — 1 Hr
  FH Rating — 2 Hr
  FTH Rating — 1 Hr
    System tested with a pressure differential of 50 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side.
    1. Wall Assembly — Min 6 in. (152 mm) thick lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete wall assembly. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 3-5/8 in.(92 mm).

    See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

    2. Through Penetrants — One nonmetallic pipe to be installed either concentrically or eccentrically within the firestop system. The annular space between the nonmetallic pipe and the periphery of opening shall be min 3/8 in. (10 mm) to max 3/4 in. (19 mm). Pipe to be rigidly supported on both sides of wall assembly. The following types and sizes of nonmetallic pipes may be used:.
      A. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in vented (drain, waste or vent) piping systems.
    3. The firestop system shall consist of the following:
      A. Packing Material — Foam backer rod firmly packed into opening as a permanent form. Packing material is to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material.
      B. Fill, Void or Cavity Material* — Caulk — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus flush with both surfaces of wall.

      RECTORSEALMetacaulk 1000 or Metacaulk 350i


XHEZ.W-J-2007 W-J-2007 XHEZ 613495002 SYSTEM Active 20140520 20140520 613495002