ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Rating - 2 Hr F Rating - 2 Hr
T Rating - 2 Hr FT Rating - 2 Hr
  FH Rating - 2 Hr
  FTH Rating - 2 Hr
    1. Wall Assembly — Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 3 in. (76 mm) or a max area of 4 in2 (25.8 cm2) with a max dimension of 2 in. (51 mm).

      See Concrete Blocks (CAZT) in the Fire Resistance Directory for names of manufacturers.

    2. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of sealant applied within annulus, flush with both surfaces of wall.

    RECTORSEALMetacaulk 1000


XHEZ.W-J-0027 W-J-0027 XHEZ 613495002 SYSTEM Active 20190506 20190506 613495002