ANSI/UL 1479 (ASTM E814)
F Rating — 2 Hr
T Rating —1-1/4 Hr
L Rating At Ambient — Less Than 1 CFM/device
L Rating At 400°F — Less Than 1 CFM/device
W Rating — Class 1 (See Item 4A and 6)
Config A
Config B
1. Floor Assembly — (Config A) Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
1A. Floor Assembly — (Config B) As an alternate to Item 1. The fire-rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below:
A. Concrete — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete.
B. Steel Floor and Form Units* — Composite or non-composite max 3 in. (76 mm) deep fluted galv units as specified in the individual Floor-Ceiling design.
2. Firestop Devices* — Cast in place firestop device permanently embedded during concrete placement in accordance with accompanying installation instructions. The devices are provided in nom 2, 3, 4 and 6 in. (51, 76, 102 and 152 mm) diam sizes. The 6 in. (152 mm) device shall only be used with PVC or CPVC penetrants (Item 3A or 3B).

RECTORSEALMetacaulk Cast-in-Place Device

3. Through Penetrants — One nonmetallic pipe centered within the firestop system. Pipe to be rigidly supported on both sides of floor assembly. The following types of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems.
C. Polypropylene Random (PP-R) Pipe — Nom 2 in. (51 mm OD) diam (or smaller) SDR 7.4 Aquatherm Green pipe for use in closed (process or supply) piping systems.

D. Polypropylene (PP-RCT) PipeNom 2 in. (51 mm OD) diam (or smaller) SDR 7.4 Niron Clima or Niron CoolPro pipe for use in closed (process or supply) piping systems.

E. Cross Linked Polyethylene (PEX) Tubing — Nom 2 in. (51 mm) diam (or smaller) SDR 9 PEX tubing for use in closed (process or supply) piping systems.
4. Pipe and Equipment Covering Materials* — Nom 1 in. (25 mm), 1-1/2 in. (38 mm) or 2 in. (51mm) thick hollow cylindrical heavy density glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product.

See Pipe and Equipment Covering — Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.

4A. PVC Jacket+ — (Optional) An additional PVC jacketing (Item 4,B), supplied in sheet form, shall be tightly wrapped around the all service jacket on the pipe covering with the longitudinal seam continuously sealed using the adhesive supplied with the jacket. The jacket is to be nom 48 in. (1219 mm) wide by nom 20 or 30 mil (0.5 or 0.8 mm) thick. The jacket shall be installed at a point 36 in. (914 mm) to 40 in. (1016 mm) above the top surface of the floor assembly and shall extend downward into and/or through the opening.

See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used.

The PVC jacket (Item 4A) is required for all fiberglass pipe coverings for the W Rating to apply.

5. Packing Material — (Optional, Not shown) - Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into the annular space as a permanent form. The packing material is to be installed flush with the top surface of the floor or recessed from the top surface of the device to accommodate the required thickness of caulk (Item 6).
6. Fill, Void or Cavity Material* — Caulk — (Optional, Not Shown) Caulk applied within device to finish flush with top surface of device. The minimum thickness and packing material shall conform to the following table:
Caulk Minimum
Thickness
In., (mm)
Device Size
In. (mm)
Packing Material
Metacaulk 835+ or Metacaulk 1200 1/4 (6) 2, 3, 4 (51, 76, 102) Min. 3 in. (76 mm) thickness of min. 4.0 pcf (64 kg/m3) mineral wool
Metacaulk 835+ or Metacaulk 1200 3/8 (10) 6 (152) Min. 3 in. (76 mm) thickness of min. 4.0 pcf (64 kg/m3)
Metacaulk 150+ or Metacaulk 1200 1/2 (13) 2, 3, 4, 6 (51, 76, 102, 152) Foam backer rod
Metacaulk 1000 1/2 (13) 2, 3, 4, 6 (51, 76, 102, 152) Min. 4 in. (102 mm)thickness of min. 4.0 pcf (64 kg/m3) mineral wool

RECTORSEALMetacaulk 150+, Metacaulk 835+, Metacaulk 1000 or Metacaulk 1200.


W Rating only applies when the optional caulk is used.

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

XHEZ.F-A-2291 F-A-2291 XHEZ 613495002 SYSTEM Active 20181204 20181204 613495002 613495002