F Rating — 2 Hr

T Rating — 1-3/4 Hr

    1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete floor or wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 6 in. (152 mm).

      See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

    2. Through Penetrant — One tube centered within opening. Tube to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic tubing may be used:
      A. Aluminum Tubing — Reflok 6061-T4 ASTM B210 seamless aluminum tubing for use in closed (process or supply) piping systems. Tubing size shall be maximum 2-1/8 in. (54 mm) to minimum 1/4 in. (6 mm) outer diameter (OD) having wall thickness ranging from 0.080 in. (2 mm) to 0.030 in. (0.8 mm) respectively.
    3. Pipe Covering — The following pipe covering shall be used with each Through Penetrant (Item 2).
      A. Tube Insulation-Plastics+ — Min 1/2 in. (13 mm) thick to max 1-1/2 in. (38 mm) thick Aerocel Ethylene Propylene Diene Terpolymer (EPDM) pipe insulation furnished in the form of tubing. The annular space between the insulated penetrant and the edge of the opening shall not exceed 3/8 in. (9.5 mm).

      See Plastics+ - (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications of having a UL 94 Flammability Classification of 94-5VA may be used.

    4. Firestop System — The firestop system shall consist of the following:
      A. Fill, Void or Cavity Material* — Wrap Strip — Two layers of nom 1/4 in. (6 mm) thick by 2 in. (51 mm) wide intumescent wrap strip wrapped around the outer circumference of the insulated pipe at bottom of floor or at each side of wall. Wrap strip installed with butted seams and located such that edge of wrap strip is flush with the surface of floor or wall. Wrap strip temporarily secured with tape or tie wire.

      RECTORSEALMetacaulk Wrap Strip, Biostop Wrap Strip or Flamesafe Wrap Strip


      B. Steel Collar — A collar fabricated from coils of precut min 0.016 in. thick (0.41 mm) galv steel available from fill material manufacturer shall be installed to retain wrap strip. Collar shall be nom 2 in. (51 mm) deep with 1 in. (25 mm) wide by 1-1/2 in. (38 mm) long anchor tabs located 4 in. (102 mm) on center for attachment to floor or wall. In addition, collar provided with 1/2 in. (13 mm) wide by 3/4 in. (19 mm) long retainer tabs opposite the anchor tabs. Collar shall be wrapped over the wrap strip, overlapping min 1 in. (25 mm) and secured with two max 3/8 in. (9.5 mm) long steel screws or stainless steel hose clamp. The retainer tabs are folded 90 deg towards the pipe to maintain the annular space around the pipe and to retain the wrap strip. Collar secured to of bottom of floor or both surfaces of wall at each anchor tab by means of 1/4 in. diam by min 1-1/4 in. (32 mm) long steel anchors in conjunction with 1/4 in. by 5/8 in. (6 by 16 mm) diam washers.
      B. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of caulk applied within annular space flush with top surface of floor. Sealant optional in walls.

      RECTORSEALMetacaulk 1000, Biostop 150+, Metacaulk 150+, Metacaulk 350i, Biostop 350i, Biostop 500+


XHEZ.C-AJ-5380 C-AJ-5380 XHEZ 613495002 SYSTEM Active 20160707 20160707 613495002 613495002