Assembly Rating — 4 Hr

L Rating at Ambient — Less than 1 CFM/Lin Ft

L Rating at 400 F — Less than 1 CFM/Lin Ft

Nominal Joint Width — 2 In.

Class II Movement Capabilities — 12.5% Compression or Extension

    1. Floor Assembly — Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100 - 150 pcf or1600-2400 kg/m3) structural concrete.
    2. Joint System — Max width of joint (at time of installation of joint system) is 2 in. The joint system is designed to accommodate a max 12.5 percent compression or extension from it's installed width. The joint system shall consist of the following:
      A. Forming Material* — Min 4 pcf (64 kg/m3) mineral wool batt insulation installed in joint opening as a permanent form. Pieces of batt cut to min width of 6 in. (152 mm) and installed edge-first into joint opening, parallel with joint direction, such that batt sections are compressed min 50 percent in thickness and that the compressed batt sections are flush with from top surface of the floor. Adjoining lengths of batt to be tightly-butted with butted seams spaced min 24 in. (610 mm) apart along the length of the joint.

      INDUSTRIAL INSULATION GROUP L L C — MinWool-1200 Safing


      JOHNS MANVILLE — Safing


      ROCK WOOL MANUFACTURING CO — Delta Safing Insulation


      ROCKWOOL MALAYSIA SDN BHD — SAFE Mineral Wool


      ROCKWOOL — SAFE Mineral Wool


      THERMAFIBER INC — SAF Mineral Wool


      B. Fill, Void or Cavity Material* - Spray — Min 1/8 in. (3.2 mm) wet thickness of fill material applied on top surface of floor to completely cover the mineral wool and overlap a min 1/2 in. (13 mm) onto concrete floor.

      RECTORSEAL — FlameSafe FS3000, Metacaulk 1200, 1500 or Biostop 750, 800 Spray


XHBN.FF-D-0022 FF-D-0022 XHBN 894121001 SYSTEM Active 20151019 20151019 894121001 880051001 383406002 116367001 P1798035 324198001 613495002